Valve design: PN40 PMO Maximum working pressure under saturated steam: 25bar g * TMO Maximum working temperature: 350℃ * PMX Maximum working pressure differential: 4bar g/12bar g/25bar g
* The working pressure difference of the trap is selected according to the user's actual working condition. The actual working pressure difference must be lower than the maximum working pressure difference of the trap, such as 4 in the range of 0.1-4bar and 12 in the range of 4.1bar-12bar. * Air vent assembly imported bimetal FeNi18Cr12/FeNi31CoCr6 are used when the operating temperature exceeds 230℃.
Material list:
Body, Bonnet
A216 WCB/A351 CF8
Cover bolts
A193 B7/A193 B8
Cover gasket
Graphite+SS304
Floats, Brackets
A240 304
Seat
A276 420
Disc
A276 440C
*Air vent assembly
A240 304+hastelloy
*Air vent assembly
FeNi18Cr12/FeNi31CoCr6
Technical Standards:
Design standard: EN 26704 Connection standard: EN 26554 Test standard: EN 26948
Installation Position:
Horizontal connection: from left to right Horizontal connection: from right to left