+86-577-67999707
Email: Address:Wuxing Avenue,Wuxing Industrial Zone,Wenzhou City, Zhejiang Province,China
Valve design: PN40
PMO Maximum working pressure under saturated steam: 32bar g
* TMO Maximum working temperature: 350℃
* PMX Maximum working pressure differential: 10bar g/14bar g/32bar g
* The working pressure difference of the trap is selected according to the user's actual working condition. The actual working pressure difference must be lower than the maximum working pressure difference of the trap, such as 10 in the range of 1-10bar and 32 in the range of 14bar-32bar.
* Air vent assembly imported bimetal FeNi18Cr12/FeNi31CoCr6 are used when the operating temperature exceeds 230℃ .
Material list:
Body, Bonnet | A216 WCB/A351CF8 |
Cover bolts | A193 B7/A193 B8 |
Cover gasket | Graphite+SS304 |
Floats, Brackets | A240 304 |
Seat | A276 420 |
Disc | A276 440C |
*Air vent assembly | A240 304+hastelloy |
*Air vent assembly | FeNi18Cr12/FeNi31CoCr6 |
* Air vent assembly imported bimetal FeNi18Cr12/FeNi31CoCr6* , can be optionally equipped with European imported bimetal, support superheated steam working conditions and high temperature working conditions.
Technical Standards:
Design standard: EN 26704
Connection standard: EN 26554
Test standard: EN 26948
Installation Position:
Vertical connection: from top to bottom
Horizontal connection: from left to right
Horizontal connection: from right to left